Cummins’ named QSK diesel sets span 600–3,500 kW standby, with separate Data Center Continuous ratings. QSK95 reaches 2,500–3,350 kW DCC. Cummins approves HHP diesel sets for HVO; HSK78 and QSK60 natural-gas units serve prime-power projects.

DieselNatural gasHVO

Verified

Visit Cummins Compare with others Request a quote

Facts

Source per value
Smallest unit kW Lowest published electrical output of one generating unit in the named Lines, in kWe. Portfolio minima may include portable models. Standby where available; kVA-only figures assume 0.8 power factor. Consult Rating basis and scope; blank when unverified.
600 7
Largest unit kW Highest published electrical output of one generating unit in the named Lines, in kWe. Standby where available; other duty and frequency bases are disclosed in Rating basis and scope. kVA-only figures assume 0.8 power factor. Mechanical output and multi-unit totals are excluded.
3,500 4
Prime mover What turns the alternator in the named lines: a reciprocating (piston) engine, a gas turbine, or both.
Reciprocating engine 1
Fuels Fuels the vendor lists for the named lines: diesel, HVO (hydrotreated vegetable oil, EN 15940), natural gas, biogas, propane, hydrogen blends.
Diesel; HVO (HHP diesel sets); Natural gas (HSK78 and QSK60 gas sets) 4
Natural gas units The vendor sells gas-fired units (natural gas, pipeline gas or LNG) in the named lines, for standby, prime or bridge power.
Yes 1
HVO approved The vendor states that the named diesel lines are approved or released for HVO (renewable diesel, EN 15940 paraffinic fuel). Blank means no such statement was found on the pages read.
Yes 4
Hydrogen Hydrogen capability exactly as the vendor states it: blend share by volume, '100% hydrogen' or 'hydrogen-ready' with its conditions. Blank when the vendor states none.
Not published
Hydrogen-capable At least one named line runs on a hydrogen blend or is sold as hydrogen-ready, per the vendor. Read the Hydrogen field for the share and conditions.
Not published
Emissions certification Emissions standards the vendor names for the named lines: US EPA Tier 2 (emergency standby) or Tier 4 Final, EU Stage V, TA Luft, CPCB IV+ (India). Certifications vary by model and market.
Not published
EPA Tier 4 Final At least one named line is offered as EPA Tier 4 Final certified (engine or genset). Blank means the vendor's pages do not say.
Not published
EU Stage V At least one named model is offered as EU Stage V compliant according to the manufacturer. Version and market matter; a blank cell means the cited material did not establish this field.
Not published
Engines Whether the vendor builds the engine or turbine itself or packages engines bought from another maker, per the vendor's own pages.
Own engines 1
Data center offer Dedicated: the vendor names a product line or program for data centers. General: a standard range the vendor documents in data center use. Rental: the vendor rents fleet units for data center bridge or backup power.
Dedicated data center line 4
Lines The product series this record covers. Ratings, fuels and emissions refer to these lines, not to the vendor's whole portfolio.
QSK23, QSK38 Centum, QSK50, QSK60, QSK78 Centum and QSK95 diesel; HSK78 (C2000N6CD) and QSK60 (C1400N6) natural gas 4
Plants Factories the vendor names for these generator sets, engines or turbines (city and country).
Not published
Capacity and lead-time news The latest dated, sourced statement on factory capacity, expansion investment or lead time for these lines, from the vendor, a filing or trade press. Month and year first.
May 2026: Cummins announced large-engine capacity and product investments for power generation at its Analyst Day; Q3 2026 Power Systems sales rose 15%, led by data center demand 2
Rating basis and scope Duty, frequency, fan allowance, conversion basis and model limitations attached to the published kWe endpoints. Mechanical engine kWm and multi-unit container or plant totals are excluded.
Named diesel envelope 600–3,500 kW standby. DQCA/QSK23: 600 kW standby, 545 kW DCC. QSK38 Centum: 1,250–1,500 kW standby. QSK78 Centum: 2,640–3,000 kW standby, 2,400–2,725 kW DCC. QSK95: 2,680–3,500 kW standby, 2,500–3,350 kW DCC; the separate numeric DCC fields cover QSK95 only. HVO statement covers HHP diesel sets. 4
QSK95 DCC minimum kW Cummins QSK95 minimum published Data Center Continuous electrical rating, in kWe; distinct from standby and prime. Not a whole-vendor minimum.
2,500 5
QSK95 DCC maximum kW Cummins QSK95 maximum published Data Center Continuous electrical rating, in kWe; distinct from standby and prime. Not a whole-vendor maximum.
3,350 5
Supply and service scope Documented generator supply, installation, commissioning and support services.
Not published
Service coverage Territories explicitly covered by the cited generator supply or service offer.
Not published

Sources

  1. Cummins: natural gas generators to power large scale data centers in West Texas (16 Jun 2026) accessed 2026-11-11
  2. Cummins: raises 2030 targets, announces large-engine capacity and product investments (21 May 2026) accessed 2026-11-11
  3. Cummins: third quarter 2026 results accessed 2026-11-11
  4. Cummins: QSK50/QSK60/QSK95 standby ranges and HHP HVO compatibility accessed 2026-11-11
  5. Cummins: QSK95 standby, prime and Data Center Continuous ratings accessed 2026-11-11
  6. Cummins: HSK78 and QSK60 gas units for West Texas data centers accessed 2026-11-11
  7. Cummins: DQCA QSK23, 600 kW standby and 545 kW DCC accessed 2026-11-11
  8. Cummins: QSK38 Centum specification sheet, standby/DCC and HVO accessed 2026-11-11
  9. Cummins: QSK78 Centum standby and DCC ranges accessed 2026-11-11

Get a quote from Cummins and similar vendors